RCD trips indicate earth leakage. This procedure is a temporary soft‑start/sequencing method to get up and running for today. Log the incident and book a service call with Solid to investigate permanent fixes (inrush management, staged power, etc.).
Not always a fault: A single trip on a very cold or damp morning doesn’t automatically mean there’s a permanent fault. Large switch‑mode power supplies (PSUs) have input EMI filters and big charging capacitors. When many PSUs start at once:
Their Y‑capacitors to earth create a small leakage current each; the sum across dozens of PSUs can momentarily exceed a 30 mA RCD threshold, especially if there’s condensation increasing surface leakage.
Cold electrolytic capacitors and PFC front‑ends draw brief, peaky currents while charging; this can nuisance‑trip upstream protection and coincide with RCD sensitivity.
Why sequencing helps: Bringing circuits up one at a time reduces the number of PSUs energising simultaneously, which cuts the instantaneous leakage/inrush and also helps identify any sub‑circuit that is genuinely leaky or damaged.
Objective: Bring circuits up one at a time to avoid a big inrush.
We are using an example of an LED screen with 4 rows of LED panels/cabinets (top, middle, bottom, plus a misc. circuit). Your configuration will most likely be different.
If you are nervous about this procedure then STOP and contact your organisation's Sparky (licenced electrician).
Power Down & Reset
Turn OFF the Main Isolator.
Ensure all MCBs (Top/Middle/Bottom/Misc) are set to OFF.
Set RCD(s) to OFF/RESET (down) as applicable.
Wait 60 seconds to allow supplies to discharge.
Energise RCD(s)
Turn ON the RCD(s) (safety switches). Confirm they stay latched.
Sequenced MCB Power‑Up
Turn ON the Main Isolator.
Turn ON MCB #1 (e.g., TOP ROW) and wait 10–15 seconds.
If no trip, turn ON MCB #2 (e.g., MIDDLE ROW). Wait 10–15 seconds.
If no trip, turn ON MCB #3 (e.g., BOTTOM ROW). Wait 10–15 seconds.
Finally, turn ON MCB #4 (MISC/AUX). Wait 10–15 seconds.
Observe the screen; confirm normal boot with no trips.
If an RCD Trips during Sequencing
Note which MCB you just turned on.
Set Main Isolator OFF.
Set the last MCB back to OFF.
Turn RCD ON (reset). Turn Main Isolator ON.
Skip the problem MCB and continue bringing others up one‑by‑one to run the rest of the screen for today.
Log the tripping MCB name (e.g., “MIDDLE ROW”) for service.
Objective: Identify which circuit is causing the trip so we can operate the remainder safely.
All OFF: Main Isolator OFF, all MCBs OFF, RCD OFF/Reset.
RCD ON: Turn on RCD(s) and confirm they latch.
Main Isolator ON.
Turn on MCBs one‑by‑one with a 10–15 sec pause between each:
If a trip occurs immediately after a specific MCB, mark that MCB as Suspect.
Reset as above, leave the Suspect MCB OFF, and continue with the remaining circuits.
Operate with Suspect MCB OFF for today. Book service ASAP to diagnose that row/section.
Operating an LED screen with a non-functional circuit will most likely affect other portions of the screen image & the daisy-chained video feed.
An RCD won’t latch even with all MCBs OFF.
Repeated trips on the same MCB after sequencing.
Visible moisture inside enclosures, damaged cables, or burning smell.
Any signs of electric shock, smoke, arcing, or heat damage.